ISO 21487:2022

Diesel Metallic Tank Compliance Checklist

With Enhanced Type Test Documentation

Small Craft - Permanently Installed Petrol and Diesel Fuel Tanks

Third Edition 2022-11

Project Information

About Type Tests for Diesel Metallic Tanks: Type tests are laboratory tests performed on representative tank samples to verify that the tank design meets all safety and performance requirements of ISO 21487:2022. For metallic diesel tanks, only TWO type tests are required: Leakage Test and Pressure/Strength Test. Unlike petrol tanks, diesel metallic tanks do NOT require the Pressure-Impulse Test or Fire Testing. Once a tank design has successfully passed type testing, individual production tanks of that design only require production quality tests (leakage test), not the full type test series.

6.2 Type Tests for Diesel Metallic Tanks (Table 2)

Type Test Overview: Per ISO 21487:2022 Table 2, metallic diesel fuel tanks must undergo TWO mandatory type tests: Pressure-Impulse Testing (Clause 7.3) and Fire Testing (Clauses 7.4 and 7.5) are NOT required for metallic diesel tanks.

Type Test 1: Leakage Test (Clause 7.2.1)

Test Purpose and Objective

The leakage test verifies the integrity of all tank seams, welds, fittings, and connections under normal operating pressure conditions. This test ensures that the diesel tank will not leak fuel during normal service use. For diesel tanks, this is particularly important as diesel fuel has different viscosity and penetration characteristics compared to petrol.

Test Procedure

Step 1: Test Setup

  • Tank must be tested with all fittings, connections, and closures installed as they would be in service
  • This includes any bottom drains, side fittings, sight gauges, and inspection hatches
  • Tank must be mounted or supported to prevent distortion during testing
  • All openings except the test pressure connection must be sealed
  • If tank has inspection hatches, ensure gaskets are properly installed and torqued

Step 2: Pressure Calculation

Calculate the required test pressure as the GREATER of:

  • 20 kPa (minimum absolute value)
  • 1.5 times the highest hydrostatic pressure to which the tank will be subjected in normal service
  • For sealed systems: 1.5 times (maximum hydrostatic head + system relief valve pressure)

Important for Diesel Tanks: Consider tank height and any pressurized fuel systems when calculating service pressure. Diesel systems may have fuel return lines under pressure.

Step 3: Pressurization Method

  • Use clean, dry air or inert gas (nitrogen recommended)
  • Gradually increase pressure to the calculated test pressure
  • Avoid sudden pressure application that could damage the tank
  • Monitor pressure gauge continuously during pressurization

Step 4: Static Pressure Hold

  • Maintain the test pressure for a minimum of 5 minutes
  • Monitor pressure gauge to ensure no pressure drop or rise occurs
  • Record initial and final pressure readings with timestamps
  • Any pressure change indicates a leak or temperature effect

Step 5: Leak Detection

  • Visual inspection: Look for bubbles using leak detection solution (soapy water) applied to all welds, seams, fittings, and connections
  • Pay special attention to inspection hatch gaskets, bottom drain connections, and sight gauge fittings (specific to diesel tanks)
  • Alternative methods: Ultrasonic leak detector, electronic gas detector
  • DO NOT rely solely on pressure drop as the only leak detection method
  • Check all threaded connections, welded joints, and gasket seals
Pass Criteria
  • No visible leakage at any point during the 5-minute test period
  • No pressure drop or rise during the static pressure hold period
  • No bubbles or leakage detected at welds, seams, fittings, or inspection hatches
  • Tank structure shows no signs of distortion or damage
  • All gaskets and seals remain intact and functional
Failure Indicators
  • Visible fuel or test gas leakage at any location
  • Continuous pressure drop indicating a leak
  • Bubbles forming at welds, seams, connections, or gaskets
  • Leakage around inspection hatch, drain valves, or sight gauge connections
  • Structural deformation or damage to tank
Special Considerations for Diesel Tanks
  • Inspection hatches (required for diesel tanks) must be leak-tested with gaskets properly installed
  • Bottom drain fittings (if present) require careful attention during leak testing
  • Sight gauge connections (if fitted) must be tested with both top and bottom valves
  • Side or bottom fittings with shut-off valves must be tested in operational configuration
Test 1: Leakage Test - Data Recording Form

Type Test 2: Pressure/Strength Test (Clause 7.2.2)

Test Purpose and Objective

The pressure/strength test verifies that the diesel tank structure can withstand pressures significantly higher than normal operating conditions without cracking or catastrophic failure. This test ensures adequate safety margins and structural integrity. Permanent deformation is acceptable, but the tank must not crack or leak. For diesel tanks, this test is particularly important for integral tanks and tanks with bottom fittings that may experience higher pressures.

Test Method Selection

There are TWO acceptable test methods per ISO 21487:2022:

  • Method 7.2.2.2 (Standard Method): Suitable for all metallic diesel tanks (both integral and non-integral)
  • Method 7.2.2.3 (Alternate Method): Only for tanks meeting specific structural and welding quality requirements
Method 7.2.2.2 - Standard Pressure Test

Applicability: All metallic diesel fuel tanks (both integral and non-integral configurations)

Test Pressure Calculation:

Test pressure must be the GREATER of:

  • 20 kPa (minimum absolute value)
  • 1.5 times the maximum hydrostatic pressure in service
  • For sealed systems: 1.5 times (maximum hydrostatic head + system relief valve pressure)

Important for Diesel Tanks: Consider maximum fuel height in the tank, especially for integral tanks. Also account for any fuel return line pressures.

Test Procedure:

  • Conduct AFTER successful completion of leakage test (7.2.1)
  • Tank may be partially or fully filled with water to simulate service conditions
  • For integral tanks, ensure mounting simulates actual installation stresses
  • Apply calculated test pressure using compressed air or inert gas
  • Maintain test pressure for minimum 5 minutes
  • Monitor for any cracks, ruptures, or leakage at all fittings
  • Permanent deformation is acceptable
Method 7.2.2.3 - Alternate Method (Qualifying Tanks Only)

Applicability Requirements:

This method may ONLY be used if ALL the following conditions are met:

  • Tank structure complies with ISO 12215-5:2019 (plating thickness, section modulus, web shear areas as for integral tanks)
  • Tank structural details follow ISO 12215-6:2008 (metal construction guidelines)
  • Welding quality meets minimum Class B per ISO 5817
  • All welders are qualified per ISO 9606 series or equivalent recognized standards
  • Complete technical drawings available showing material grades, thicknesses, dimensions, welding details
  • For integral tanks: Structural calculations must demonstrate compliance with ISO 12215-5:2019

Test Pressure Calculation:

Test pressure must be the GREATER of:

  • 30 kPa (minimum absolute value - note this is HIGHER than standard method)
  • 1.5 times the maximum hydrostatic pressure in service + 10 kPa

Test Procedure:

  • Same procedure as Method 7.2.2.2
  • Apply calculated test pressure for minimum 5 minutes
  • Monitor for cracks, ruptures, or leakage
  • Permanent deformation is acceptable
  • For integral tanks, pay special attention to hull interface areas
Pass Criteria (Both Methods)
  • No cracks develop anywhere in the tank structure
  • No rupture or catastrophic failure occurs
  • No fuel leakage detected during or after test
  • Tank maintains pressure for full 5-minute duration
  • Permanent deformation is acceptable (tank does not need to return to original shape)
  • Inspection hatch gaskets remain sealed (if applicable)
  • Bottom fittings and drain valves show no leakage (if applicable)
  • For integral tanks: No delamination or separation from hull structure
Failure Indicators
  • Any crack formation in welds, seams, or base material
  • Rupture or catastrophic structural failure
  • Leakage of test medium at any location
  • Inability to maintain test pressure for 5 minutes
  • Gasket failure at inspection hatch
  • Leakage at bottom drain or sight gauge connections
  • For integral tanks: Separation or delamination from hull
Special Considerations for Diesel Tanks
  • Integral tanks require special attention to hull-to-tank interface during testing
  • Bottom fittings and drain valves (common in diesel tanks) are stress concentration points
  • Inspection hatches must be tested with full gasket compression
  • Consider additional test cycles if tank shows deformation near critical fittings
Important Note on Alternate Method 7.2.2.3:

Before selecting the alternate method, verify that your tank design meets ALL structural and welding requirements. This is especially critical for integral diesel tanks. If you are unsure, use the standard method 7.2.2.2. Using the alternate method without meeting all requirements invalidates the test results.

Test 2: Pressure/Strength Test - Data Recording Form
Important Note - Diesel Tank Type Testing Simplification:

Unlike petrol tanks which require three type tests (Leakage, Pressure/Strength, and Pressure-Impulse), metallic diesel tanks only require TWO type tests:

The following tests are NOT required for metallic diesel tanks:

This makes diesel metallic tank type testing significantly faster and less expensive than petrol tank testing.

Type Test Summary and Compliance Status

Type Test Results Overview: Review the results from both mandatory type tests. The diesel metallic tank design can only be considered compliant with ISO 21487:2022 if BOTH tests have been passed successfully.
Test Number Test Name ISO Clause Required for Diesel Metallic? Status Test Date
1 Leakage Test 7.2.1 YES - REQUIRED Not Tested -
2 Pressure/Strength Test 7.2.2 YES - REQUIRED Not Tested -
3 Pressure-Impulse Test 7.3 NO - Not Required Exempt N/A
4 Fire Testing 7.4/7.5 NO - Metallic Exempt Exempt N/A
Overall Type Test Status: Not Complete

Test Report Certification

ISO 21487:2022 - Small Craft - Permanently Installed Petrol and Diesel Fuel Tanks

Third Edition 2022-11

This checklist references ISO 21487:2022 for informational purposes only.

ISO standards are copyright of the International Organization for Standardization.

Users must obtain the official standard from ISO or authorized distributors.

Powered by Blue Peter Marine

www.ceinspector.com